Wednesday, 07 October 2015 14:11

Understanding the C8 Board - Part 4 - Jumpers

In previous parts of this series, we have covered the very basics and the inputs and outputs of the C8 board.  If you missed these parts, you can find them here:

Part 1 - Power and LEDs
Part 2 - Inputs
Part 3 - Outputs

This week we will cover in detail the jumper configuration of the C8 board.

General Jumper Setting Information

First, it is important to verify the voltage of the power supplies and to set the C8 jumpers before connecting any load.  This is to ensure the proper voltage is sent to the load devices and prevent damage to the devices.  Verify output voltage on each zone before connecting any load.

If you have read the previous parts of this series, you should have a fairly solid understanding of how the C8 should operate.  This knowledge is helpful in setting the jumpers when a manual is not available.  As mentioned in previous posts, it is not necessary to have the function of each jumper's positions memorized - only the overall function of the jumper.  For example, once you know the Red jumper is for FAI, you know that is the jumper to move if FAI is not operating the way you expect it to for a particular zone.  There is no need to memorize that Position 1 is on, and position 2 is off, or that position 2 of the Blue jumper is for a NO input.  As you go through the following sections, take note of the jumper color in relation to its function.

Also remember the correct LED operation - LED lit steady for a locked door, and flashing for an unlocked door.  The goal is to get this correct with relation to the input, then set the output to operate correctly.

Finally, please note jumper positions as they are printed on the PC boards carefully for EACH jumper.  For some jumpers, position 1 is up, while for others, position 1 is down.  Every jumper has a position marker next to it.

Black Jumpers

The black jumpers select whether the output will be a relay contact output or a wet (voltage) output.  Both jumpers should always be set in the same position, without exception.  Use caution when setting these jumpers, as position 1 is different on each jumper.  From the factory, these jumpers come set in position 2, which provides a voltage output.  If a relay output is desired, move these jumpers to position 1.

Yellow Jumper

The yellow jumper selects the voltage to be applied to the zone's output.  Position 1 sets the output to the B1 voltage, and position 2 sets it for the B2 power supply.  In a single voltage system, this jumper will remain in position 1, as there is no B2 voltage present.

In a dual FPO system, as built by LSP, the top FPO will be the B1 voltage.  The bottom FPO will be the B2 voltage.  So if the top power supply is set for 24V and the bottom FPO is set for 12V, then position 1 on the yellow jumper will set the output for 24V, position 2 for 12V.  In an FPO/B100 system, the 24V is on B1, and the B100's output is on B2.

Again, always verify each zone's output voltage before connecting any load to the C8.

Blue Jumper

While all of the jumper settings are equally important, getting the blue jumper set properly is critical to the operation of the C8.  In Part 2, we discussed how the B terminal of the input is a voltage input, while the A terminal is a voltage source.  The blue jumper sets the zone to either activate on the application of voltage, or the removal of voltage on the B terminal.

Position 1 will activate the zone on a removal of voltage from the B terminal.  This is the setting you would want for a NC contact activation.  The NC contact will normally connect the voltage from the A terminal to the B terminal.  When the NC contact opens, the voltage at the B terminal goes to zero, and activates the zone.  This is also the setting to be used for an open collector input - normally, a voltage is present on the B terminal, and the open collector will shunt this voltage to zero to activate the input.

Position 2, is the opposite - an application of voltage will activate the zone.  This is the setting to use for a normally open contact activation.  When the contact closes, it connects the voltage from the A terminal to the input of the B terminal to activate the zone.

To verify the proper setting of the blue jumper, look at the LED status for the zone in relation to the input.  If the LED is flashing when the input is set to unlock the door, the blue jumper is set correctly.  If the output is operating opposite from what is expected, but the LED is operating correctly, then the white jumper needs to be adjusted.

White Jumper

The white jumper sets the output by selecting the NO or NC contact of the internal relay contact.  Position 1 uses the NC contact and position 2 uses the NO contact.  When set for a relay output, this is straightforward.  When set for a voltage output, position 1 should be used for a doorstrike, electrified handleset,  or other fail-secure device.  Position 2 would be used for a maglock or other fail-safe device.

If the output is operating backwards from what is expected but the LED is indicating correctly with relation to the input, the white jumper should be changed.

Red Jumper

The red jumper sets the FAI activation of the zone.  Position 1 enables FAI activation, while position 2 deactivates FAI for the zone.  The setting of the blue jumper is crucial to proper FAI operation.  Remember that the LED for the zone should flash when the door is unlocked.  If the blue jumper is set incorrectly, the LED will be flashing when the door is locked.  This presents a problem when an FAI activation is received because the C8 thinks the door is already unlocked, so the output does not change.  If the LED is operating backwards from what is intended, move the Blue and White jumpers to the opposite position that they are currently in and FAI should begin working properly.

Settings Chart

The manual for the C8 board has a very helpful chart for jumper settings.  The Common Jumper Settings chart is organized by output type.  Find the desired output type, then look down to find the desired input type.  Then select With or without FAI and look across the row for the jumper settings for that configuration.  This chart covers 99 percent of common applications.

Next Week

Next week we will cover the usage of our Excel-based C8 Jumper Configuration Tool for help with jumper settings.  Until then, if you need any assistance, our This e-mail address is being protected from spambots. You need JavaScript enabled to view it is here to help.

Published in Blog
Tuesday, 25 August 2015 15:47

Understanding the C8 Board - Part 1

LifeSafety Power's FlexPower line of power systems is the industry's first and only fully-modular, listed power supply system.  This allows you to choose from a variety of power supplies and output boards and combine them in the best combination for the job at hand.  One of the most versatile components at your disposal is the C4 or C8 lock control board.  Don't let the "lock control" fool you, however - the C4 and C8 can do far more than just locks. 

C4C8Photo

The C4 and C8 come in four different variations.  The C4 and C8 provide 4 and 8 zones, respectively, of 3A fused outputs.  The C4P and C8P provide the same 4 and 8 zone counts but use 2.5A PTCs, rather than fuses, to provide Class 2 Power Limiting.  In this multi-part series of posts, we will refer mostly to the C8 board, but the C8P, C4, and C4P are all identical in operation.

What does the C8 do?

The C8 board provides eight outputs, each with its own input for control.  If you are familiar with the Altronix ACM8, then you are already familiar with this basic concept.  The inputs of the C8 are low current, protecting your high-cost access control panel's relays from the high currents and return EMF spikes from the locks.  Each output can be individually selected for voltage, lock type, input type, and whether or not to unlock the door on a Fire Alarm Input (FAI) activation.  Outputs can be wet or dry (NO or NC).

Input Power & FlexIO Connections

Like all FlexPower output boards, the C8 has a dual-buss power input, allowing use in either single or dual voltage power supplies.  When used in a dual voltage power supply, the C8 allows you to select either voltage on each individual output.  Note that the C8 MUST be supplied with constant power for proper operation.  Do not use the DC2 output of the FPO power supply to power the C8 board - the C8 controls each output for FAI on its own.

C8Power

The first power supply should be connected to the B1 input of the C8.  As with all FlexPower output boards, the power connections can be made at either B1 terminal.  The BR connection serves as the DC common and must be connected to the BR terminal of the power supply.

If a second power supply is also being used, it should be connected to the B2 input of the C8.  The second power supply's BR terminal must also be connected to the other BR terminal of the C8 so that everything is common grounded together.

The FlexIO connectors supply FAI input and fault status to and from the C8 board.  Both FlexIO connectors are the same and either may be used interchangeably.  Simply plug one end of the white 2-pin FlexIO cable into the FPO power supply's FlexIO connector and the other end into the C8.

If there are other output boards already connected to the power supply, the C8 may be connected at the end of the chain, or inserted into the middle of the chain.  Make sure to match up the wire colors and B1/B2 connections to the other boards in the system.

Visual Indicators

The C4 and C8 boards have a green LED for every output indicating its status.  When the C8 is properly configured, a steady green LED indicates that the door is locked, and a flashing green indicates unlocked.  Notice we are speaking in terms of "locked" and "unlocked" rather than about the outputs being powered and unpowered.  This makes understanding and configuring the C8 easier, once you are accustomed to thinking this way - all LEDs function the same, whether the input is NO or NC, whether the output is connected to a maglock or door strike, whether FAI is active or not.

If any of the green LEDs are out, it indicates that there is a problem with the fuse (or PTC), jumper settings, or there is a missing power supply voltage.

The C4 and C8 also have a single yellow fault LED.  It will light whenever any of the green LEDs are out (blown fuse, incorrect jumper setting, or missing power supply voltage).  If there is a fault on your FPO power supply and the C8 also indicates a fault, correcting the C8 fault will likely clear the FPO fault unless multiple problems exist in the system.

Next Week

This week we covered some of the very basics of the C8.  In the next post in this series, we will go even more in-depth on the inputs of the C8 board - including wiring, configuration, and other information. Until then, if you need any assistance our This e-mail address is being protected from spambots. You need JavaScript enabled to view it department is always here to help. 

Published in Blog