BluBox Integration

NetLink integration with BluB0X provides alerts, measurements, and control capabilities to BluSKY.  Power system alerts, measurements, and system control features are available directly from the BluSKY interface, streamlining system maintenance and maximizing system uptime.

Integration to BluSKY is via PSIA/XML and is supported by BluB0X.

Requirements & Information

ItemInformation 
BluSKY Version Supported 
BluB0X License Required 
NetLink Boards SupportedNL2, NL4
NetLink Minimum Firmware Version9.18 or above
Integration TypePSIA / XML
Integration LevelFull

 

Supported Alerts

AlertSupported 
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

 

Values Reported

ValueSupported
AC Input Voltage 
Power Supply Output Voltage●
Power Supply Total Output Current 
Battery Voltage●
Battery Charge / Discharge Current●
M8 Output (Lock) Voltage●
M8 Output (Lock) Current●
M8 Output (Lock) Cycle Count 
Enclosure Temperature●
External Temperature (IDF Closet)●
Current Sensor Measurement●
Auxiliary Voltage Measurement●

 

Control Features

Control ItemSupported
Start / Schedule Automated Battery Test ●
Power Cycle M8 Output ●
Power Cycle Power Supply Main Output ●
NetLink Control 1 / Control 2 Outputs ●