Print

RS2 Integration

NetLink integration with RS2 provides alerts and control capabilities to Access It! Universal.NET.  Power system alerts and system control features are available directly from the Access It! interface, streamlining system maintenance and maximizing system uptime.

Integration to Access It! is via the native Mercury Integration and is supported by RS2.

New RS2 Logo
 
Requirements & Information
ItemInformation
Access It! Universal.NET Version Supported6.1 or higher
RS2 License RequiredNone
NetLink Boards SupportedNL2, NL4
NetLink Minimum Firmware Version9.18 or above
Integration TypePSIA / XML
Integration LevelAlerts & Control

Supported Alerts
AlertSupported
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

Values Reported
ValueSupported
AC Input Voltage 
Power Supply Output Voltage 
Power Supply Total Output Current 
Battery Voltage 
Battery Charge / Discharge Current 
M8 Output (Lock) Voltage 
M8 Output (Lock) Current 
M8 Output (Lock) Cycle Count 
Enclosure Temperature 
External Temperature (IDF Closet) 
Current Sensor Measurement 
Auxiliary Voltage Measurement 

Control Features
Control ItemSupported
Start / Schedule Automated Battery Test ●
Power Cycle M8 Output ●
Power Cycle Power Supply Main Output ●
NetLink Control 1 / Control 2 Outputs ●