PDF Print E-mail

Feenics Integration

NetLink integration with Feenics provides alerts and control capabilities to Keep.  Power system alerts and system control features are available directly from the Keep interface, streamlining system maintenance and maximizing system uptime.

Integration to Keep is via the native Mercury Integration and is supported by Feenics.

Feenics logo
 
Requirements & Information
ItemInformation
Keep Version Supported 
Feenics License RequiredNone
NetLink Boards SupportedNL2, NL4
NetLink Minimum Firmware Version9.18 or above
Integration TypePSIA / XML
Integration LevelAlerts & Control

Supported Alerts
AlertSupported
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

Values Reported
ValueSupported
AC Input Voltage 
Power Supply Output Voltage 
Power Supply Total Output Current 
Battery Voltage 
Battery Charge / Discharge Current 
M8 Output (Lock) Voltage 
M8 Output (Lock) Current 
M8 Output (Lock) Cycle Count 
Enclosure Temperature 
External Temperature (IDF Closet) 
Current Sensor Measurement 
Auxiliary Voltage Measurement 

Control Features
Control ItemSupported
Start / Schedule Automated Battery Test ●
Power Cycle M8 Output ●
Power Cycle Power Supply Main Output ●
NetLink Control 1 / Control 2 Outputs ●
 
PDF Print E-mail

Software House Integration

NetLink integration with Software House C●CURE9000 provides full power system monitoring and control capabilities to C●CURE.  Power system alerts, parameter measurements, and system control features are all available directly from the C●CURE interface, streamlining system maintenance and maximizing system uptime.

Integration to C●CURE is via a driver download. Before installing, a license must be obtained from Software House.

Compatibility Matrix

CCURE logo
 
 
Download
DescriptionLatest RevisionSoftware FileUser ManualRelease Notes
C●CURE 2.9 Integration8.9.6.29DownloadIMRN
C●CURE 2.8 Integration8.9.6.28DownloadIMRN
C●CURE 2.7 Integration8.8.9.27DownloadIMRN

Requirements & Information
ItemInformation
C●CURE Version Supported2.7, 2.8, 2.9
Software House License RequiredYes
NetLink Boards SupportedNL2, NL4, NLX
NetLink Minimum Firmware Version9.18 or above
Integration TypeNative
Integration LevelFull Integration

Supported Alerts
AlertSupported
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

Values Reported
ValueSupported
AC Input Voltage ●
Power Supply Output Voltage ●
Power Supply Total Output Current ●
Battery Voltage ●
Battery Charge / Discharge Current ●
M8 Output (Lock) Voltage ●
M8 Output (Lock) Current ●
M8 Output (Lock) Cycle Count ●
Enclosure Temperature ●
External Temperature (IDF Closet) ●
Current Sensor Measurement ●
Auxiliary Voltage Measurement ●

Control Features
Control ItemSupported
Start / Schedule Automated Battery Test ●
Power Cycle M8 Output ●
Power Cycle Power Supply Main Output ●
NetLink Control 1 / Control 2 Outputs ●
 
PDF Print E-mail

Genetec Integration

NetLink integration with Genetec's Security Center provides full power system monitoring and control capabilities to Security Center.  Power system alerts, parameter measurements, and system control features are all available directly from the Security Center interface, streamlining system maintenance and maximizing system uptime.

Integration to Security Center is via the LSPEntity software package.  LSPEntity allows adding NetLink devices into Genetec's Security Center as an Entity. Before installing, a license must be obtained from Genetec under part number GSC-1SDK-LSP-NetLink.

Genetec Security Center Integration

genetec sc logo
 
 
Download
DescriptionLatest RevisionSoftware FileUser ManualRelease Notes
LSPEntity Genetec Integration2.15DownloadIMRN

Requirements & Information
ItemInformation
Security Center Version Supported5.7, 5.8, 5.9, 5.10, 5.11
Genetec License RequiredGSC-1SDK-LSP-NetLink
NetLink Boards SupportedNL2, NL4, NLX
NetLink Minimum Firmware Version9.18 or above
Integration TypeSNMP Trap
Integration LevelFull Integration

Supported Alerts
AlertSupported
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

Values Reported
ValueSupported
AC Input Voltage ●
Power Supply Output Voltage ●
Power Supply Total Output Current ●
Battery Voltage ●
Battery Charge / Discharge Current ●
M8 Output (Lock) Voltage ●
M8 Output (Lock) Current ●
M8 Output (Lock) Cycle Count ●
Enclosure Temperature ●
External Temperature (IDF Closet) ●
Current Sensor Measurement ●
Auxiliary Voltage Measurement ●

Control Features
Control ItemSupported
Start / Schedule Automated Battery Test ●
Power Cycle M8 Output ●
Power Cycle Power Supply Main Output ●
NetLink Control 1 / Control 2 Outputs ●
 
PDF Print E-mail

LenelS2 Integration

NetLink integration with LenelS2 OnGuard provides full power system monitoring and control capabilities to OnGuard.  Power system alerts, parameter measurements, and system control features are all available directly from the OnGuard interface, streamlining system maintenance and maximizing system uptime.

Integration to OnGuard is through integration software via OAAP. 

LenelS2 OAAP Integration

LenelS2 OnGuard
 
 
 
 
 
Download
DescriptionLatest RevisionSoftware FileUser ManualRelease Notes
LenelS2 OnGuard Integration1.12DownloadIMRN

Requirements & Information
ItemInformation
OnGuard Version Supported7.6, 8.0
OnGuard License RequiredYes - See Below
NetLink Boards SupportedNL2, NL4, NLX
NetLink Minimum Firmware Version9.18 or above
Integration TypeSNMP Trap
Integration LevelAlerts

License  Numbers (Purchased through LenelS2)
SKUDescription
IPC-321-LSP01-BIf System Purchased Through LenelS2 Direct - Initial License - 10 Panels / power devices
IPC-321-010If System Purchased Through LenelS2 Direct - License and support of 10 additional panels / power devices
IPC-344-LSPZ01-BIf System Not Purchased Through LenelS2 Direct - Initial License - 10 Panels / power devices
IPC-344-010If System Not Purchased Through LenelS2 Direct - License and support of 10 additional panels / power devices
Contact LenelS2 for more licensing information.

Supported Alerts
AlertSupported
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

Values Reported
ValueSupported
AC Input Voltage 
Power Supply Output Voltage 
Power Supply Total Output Current 
Battery Voltage 
Battery Charge / Discharge Current 
M8 Output (Lock) Voltage 
M8 Output (Lock) Current 
M8 Output (Lock) Cycle Count 
Enclosure Temperature 
External Temperature (IDF Closet) 
Current Sensor Measurement 
Auxiliary Voltage Measurement 

Control Features
Control ItemSupported
Start / Schedule Automated Battery Test 
Power Cycle M8 Output 
Power Cycle Power Supply Main Output 
NetLink Control 1 / Control 2 Outputs 
 
PDF Print E-mail

BluB0X Integration

NetLink integration with BluB0X provides alerts, measurements, and control capabilities to BluSKY.  Power system alerts, measurements, and system control features are available directly from the BluSKY interface, streamlining system maintenance and maximizing system uptime.

Integration to BluSKY is via PSIA/XML and is supported by BluB0X.

BLluSKY LOGO
 
Requirements & Information
ItemInformation
BluSKY Version Supported 
BluB0X License Required 
NetLink Boards SupportedNL2, NL4
NetLink Minimum Firmware Version9.18 or above
Integration TypePSIA / XML
Integration LevelFull

Supported Alerts
AlertSupported
AC Fault Alert ●
System Fault Alert ●
Fire Alarm Active ●
Power Supply Service Due ●
Insufficient Battery Standby Time ●
Battery Replacement Due ●
M8 Output Voltage Out of Range ●
M8 Output Current Out of Range ●
Enclosure Temperature Out of Range ●
External Temperature (IDF Closet) Out of Range ●
Tamper Switch Alert ●
Device Detect (Connected or disconnected from NetLink) ●
Current Sensor Out of Range ●
Auxiliary Voltage Out of Range ●

Values Reported
ValueSupported
AC Input Voltage 
Power Supply Output Voltage
Power Supply Total Output Current 
Battery Voltage
Battery Charge / Discharge Current
M8 Output (Lock) Voltage
M8 Output (Lock) Current
M8 Output (Lock) Cycle Count 
Enclosure Temperature
External Temperature (IDF Closet)
Current Sensor Measurement
Auxiliary Voltage Measurement

Control Features
Control ItemSupported
Start / Schedule Automated Battery Test ●
Power Cycle M8 Output ●
Power Cycle Power Supply Main Output ●
NetLink Control 1 / Control 2 Outputs ●